125 kW / 261 kWh in a 1.4 m² footprint

261 kWh in a 1050 × 1350 mm footprint

Optimal in-pack duct design achieves highly efficient cooling with low energy consumption

In-pack fire warning and aerosol protection prevent heat diffusion and thermal runaway

≥ 8,000 cycle life with excellent battery system performance

| Specification | Models | Power-Source-125K/261LA |
|---|---|---|
| DC Side | Cell Type | LFP / 314 Ah |
| Pack Configuration | 52.2 kWh / 1P52S | |
| System Configuration | 261 kWh / 1P260S | |
| Rated DC Voltage | 832 V | |
| DC Voltage Range | 728 ~ 936 V | |
| Max. Charge/Discharge Rate | 0.5 P | |
| Rated Output Power | 125 kW | |
| AC Side | Rated AC Voltage | 400 V |
| AC Voltage Range | ± 15 % | |
| Grid Type | 3P + N + PE | |
| Rated Frequency | 50 Hz / 60 Hz | |
| Power Factor | 0.99 / -1 ~ +1 | |
| THDi | ≤ 3 % | |
| DC Ratio | < 0.5 % Ipn | |
| Max. Round Trip Efficiency | 89 % | |
| General | Cycle Life | ≥ 8,000 Cycles |
| Communication | Modbus TCP/IP | |
| Fire Protection System | Aerosol, Water Firefighting Interface | |
| Ingress Rating | IP55 | |
| Cooling Method | Liquid-Cooled + Forced-Air-Cooled | |
| Operating Temperature | -25 ~ 55 °C (Derating Above 45 °C) | |
| Corrosion Resistance | C4 (C5 Optional) | |
| Humidity | 0 ~ 95 % RH (Non-Condensing) | |
| Noise | ≤ 75 dB | |
| Altitude | 3000 m (Derating Above 2000 m) | |
| Dimensions (W × D × H mm) | 1050 × 1350 × 2400 mm | |
| Weight | 2600 kg | |
| Safety/EMC Standard | UN38.3, IEC62619, IEC63056, IEC62477-1, IEC61000-6-2/-4, IEC62933, MSDS | |
| Grid Connection Standard | EN50549-1/-10, EN50549-2/-10, G99, VDE4105, NRS097, C10/11, CEI0-21, CEI0-16 |